Part Number: ETI0001-2205A3
Rugged MilSpec 5000 VA UPS
120 VAC Power Source with
3-Phase Input and 1-Phase Output
Lockheed Martin AN/TPS-59 Radar System
Rugged MilSpec Rack Mount 5.0 kVA UPS
w/ 3-Phase Input, 1-Phase
Output, Remote Battleshort,
and Remote Emergency Power Off

P/N: ETI0001-2205A3 Rugged MilSpec UPS Standard Front Panel Layout
with 3U and 2U Battery Shown in Rack Mount Configuration

P/N: ETI0001-2205A3
Rugged MilSpec UPS Standard Rear Panel Layout
with 3U and 2U Battery Shown in Rack Mount Configuration
The field proven Military Power® UPS line is ideally suited for military,
industrial, computer and telecommunications applications requiring high reliability, rugged
construction, compact size and light weight design. These units are equally
suited for use in shipboard, airborne, vehicular, field deployed or fixed
locations with controlled or uncontrolled environments. The ETI0001-2205A3 is being used by Lockheed Martin as the
power source for the AN/TPS-59 Radar System because of the stringent performance
and reliability requirements.
The heavy-duty UPS and Battery chasses have rounded metal corners and rugged handles front
and rear, aiding in safe handling. Internally, all major components are well
secured and electrically insulated to prevent damage due to shock and
vibration. The internal intelligent thermal sensors provide monitoring of unit temperatures, with both local and remote Battleshort override capability of thermal shutdown for emergency scenarios. Battleshort can be engaged via a remote contact input or via a software command. When in Battleshort, an audible alarm is sounded and an indicator is lit. The high intensity audible alarm can be heard in high noise environments and includes an audible enable/disable switch.
The internal shielded
input transformer provides galvanic isolation with provisions for nominal 208 VAC, 3-phase input
voltages. Special EMI/RFI filters, input power factor correction and inrush current limiting minimize both input current and harmonics.
The unit can also operate as a frequency converter, taking 46-70 hertz input and
converting it to clean, uninterruptible 60 hertz power.
The LED arrays keep the operator
informed as to the unit's status including load and battery levels. The
high intensity audible alarm can be heard in high noise environments. All
controls and protective devices are brought to the front and rear panels with critical
switches having finger guards. The front panel also provides easy access to both the AC Input and Battery Input fuses. Coupled with the onboard spare fuses, MTTR is reduced to less than 15 minutes. Further, all front panel devices are recessed to
prevent damage or accidental operation. The
input circuit breaker and the galvanic isolation transformers
all provide a double pole isolated source for all installations including shipboard systems or
overseas locations where phase references and grounding are not consistent.
The rear panel provides locking connectors for the input
and output power. Removable, washable air filters combined with high capacity
stainless steel ball bearing fans provide added protection in both controlled and hostile
environments. The exhaust air is diverted out the rear vents, with
alternate air flow directions optional. The external battery connector allows the safe and easy addition of
the standard or extra battery modules without having to shut the unit down.
The batteries are maintenance free with immobilized electrolyte and are
constructed of flame retardant materials. For more information, see the Battery
Technology section. The
Status connector provides an interface with optional computer software
providing loss of AC and low battery status as well as remote shut down
capability.
See
ETI0001-2205A3AA for
a newer upgraded version of this unit that is totally backward compatible.
See the Power Distribution Units section for a
listing of stand alone PDUs. See the N5 Series section for
versions of UPS with an integrated PDU and remote control.
Overall, the Military Power line is uniquely qualified for critical
shipboard, vehicle, airborne or land based systems combining advanced modular design
features with highly reliable construction.
Technical Specifications:
P/N: ETI0001-2205A3
| AC OUTPUT |
| Output voltage: |
120 VAC true sinewave standard, up to 600 VAC optional |
| Output rating: UPS |
5000
VA 0.8 pf standard |
| Non-linear load capacity: UPS |
Up to 100% non-linear load capability w/o
derating |
| Output voltage regulation: UPS |
± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
| Overload surge capacity: UPS |
110% for 10 minutes; 125% for 30 seconds |
| Harmonic distortion: UPS |
Less than 5.0% into 100% non-linear load |
| Output frequency: UPS |
60 Hz ± 1.0% independent of input frequency
50, 400 or 1000 Hz
output available as an option |
| Operational status |
AC Input status, UPS operational,
UPS alarm, Battery level, Low battery, Load level, Overload, Warm
temperature, Hot temperature, Fan fail and
Battleshort LEDs,
Alarm contacts for Loss of AC and Low Battery
+90 dB audible alarm with audible on/off switch
SNMP/HTTP, Optional Asynchronous serial COM
port |
| AC INPUT |
| Input voltage: |
Nominal
208 VAC L-L, 3-phase |
| Input voltage tolerance: UPS |
148-234 VAC @ full load without
using battery, to 123 VAC @ 75% load |
| Input frequency: |
From 46 Hz to 70 Hz standard,
optional to 440 Hz |
| Input power factor: |
Better than 99% typically |
| Input/output isolation: |
6000 VA, up to 120 dB common mode, <1.0
mA
leakage |
| Input transient suppression: |
Complies with IEEE 587 and UL 1449 |
| Input control/protection: |
Guarded 3 pole 100 G shock rated circuit
breaker (CB1)
plus UPS input fuses (F2A, F2B and F2C) |
| Input power connections: |
MS 3102R-24-22P, 4 pin, locking |
| EXTERNAL BATTERY |
| External battery type: |
Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
| External battery life: |
Rated for continuous service life of 5 years |
| External DC protection: |
Front panel mounted fuses (F1A, F1B and F1C) |
| Battery expansion: |
Up to 24 hours w/ Battery Expansion Modules |
| DISTRIBUTION PANEL |
| Output circuits: |
Two AC outputs
standard |
| Output control: |
Circuit breakers (CB2 and CB3)
Remote ON/OFF of each load
Battleshort to inhibit shutdown when engaged
Remote Emergency Power Off (REPO) |
| Output receptacles: AC output |
MS3102R22-2 and MS3102R22-2SW
3-pin locking standard |
| MECHANICAL |
Dimensions (H x D x W):
UPS Module
3U Battery Module
2U Battery Module |
8.75 (5U) x 23.5 x 19.0 in (222
x 597 x 483 mm)
5.25 (3U) x 23.5 x 19.0 in (133
x 597 x 483 mm)
3.50 (2U) x 23.5 x 19.0 in (89 x 597 x 483 mm) |
| Rack Slide Mount Patterns: |
Jonathan, General Devices
patterns, others optional |
| Alternate Mounting Options: |
Table, Wall, Floor, Portable,
Horizontal/Vertical |
Unit weight:
UPS Module
3U Battery Module
2U Battery Module |
95 lb. (43 kg) UPS with lift
handles front and rear
102 lb. (46 kg) Battery with lift handles front and rear
102 lb. (46 kg) Battery with lift handles front and rear |
| Audible noise: |
Less than 59 dB @ 5.0 ft., ANSI "A"
scale |
| Cooling type: |
High capacity, positive pressure, forced air |
| Cooling air direction: |
Rear intake, exhaust to front,
others optional |
| Air intake filter: |
Washable metal filter media, others optional |
| ENVIRONMENTAL |
| Storage temperature: |
-40° to 158° F ambient (-40° to 70° C) with fully charged batteries |
| Operating temperature: |
-4° to 131° F ambient ( -20° to 55° C), lower/ higher optional |
| Operating humidity: |
0 to 95% relative humidity (non-condensing) |
| Storage elevation: |
Up to 45,000 ft (13,716 m) |
| Operating elevation: |
Up to 15,000 ft (4,572 m), higher optional |
| STANDARDS |
| United States: |
Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810F, 901D Grade A, 1399-300A & 2000
|
| Canada: |
CSA C22.2 No. 107 UPS safety requirements |
| EMI Protection: |
EMI/RFI FCC Part 15, Class A;
EN55022; MIL
STD 461E |
| OPTIONAL ACCESSORIES |
| |
Autoranging International Input,
Emergency Power Off, Elapsed Time Meter, Alternate I/O Configurations, Battery Expansion, Batteryless Operation, Battery
Charger/Conditioner, Power Distribution Units, Software
Interface, Asynchronous serial COM port, 10BaseT
Ethernet SNMP/HTTP port, Transport Cases,
Slides and Mounting Kits |